View fullsize
Australian Unity Carlton Wellbeing Centre Victoria
Independent low-care accommodation for 360 people
Client: Richstone Group
Solar pre-heated; 1000mJ gas fired, reticulated commercial hot water system.
Peak Hour Demand: 4,410-litre @ 65 Deg C
Recovery Rate: 3,780-litres per hour @ 50 Deg C rise
Solar System: 7000 litre storage 1080 evacuated tubes
Solar Contribution: 7,000-litres per day @ 50 Deg C rise – annually averaged
Model: SG2-250-315e x 2
Model: G2SS1000 x 7
Model: G2EVT x 1080
View fullsize
St Vincent Private Hospital Melbourne Victoria
Client: Regional Plumbing
Solar pre-heating to an existing commercial hot water system
Solar System: 1600 litre solar storage 180 evacuated tubes
Solar Contribution: 1,170-litres per day @ 50 Deg C rise – annually averaged
Model: G2SS800 x 2
Model: G2EVT x 180
View fullsize
Arcare ACF Hope Island Queensland
120-bed aged care facility
Client: Pipewise Plumbing
Solar pre-heated; 1000mJ gas fired, reticulated commercial hot/warm water system.
Peak Hour Demand: 4,410-litre @ 65 Deg C
Recovery Rate: 3,780-litres per hour @ 50 Deg C rise
Solar System: 4000 litre storage 480 evacuated tubes
Solar Contribution: 3,300-litres per day @ 50 Deg C rise – annually averaged
Model No: SG2-250-315i x 2
Model No: G2SS1000 x 4
Model No: G2EVT x 480
View fullsize
Nazareth House ACF Wendouree Victoria
145-bed aged care facility
Client: Premier Plumbing
Solar pre-heated; 1500mJ gas fired, reticulated commercial hot water system.
Peak Hour Demand: 6,615-litre @ 65 Deg C
Recovery Rate: 5,670-litres per hour @ 50 Deg C rise
Solar System: 3000 litre storage 360 evacuated tubes
Solar Contribution: 2,270-litres per day @ 50 Deg C rise – annually averaged
Model No: SG2-250-315e x 3
Model No: G2SS1000 x 3
Model No: G2EVT x 360
View fullsize
Peninsula Grange ACF Mornington Victoria
102-bed aged care facility
Client: MAACC Pty Ltd
Supply, installation and commissioning of a solar pre-heated; 1000mJ gas fired external, reticulated commercial hot and warm water system
Peak Hour Demand: 5,080-litres @ 65 Deg C
Recovery Rate: 3,780-litres @ 50 Deg C rise
Solar System: 4000 litre solar storage 480 evacuated tubes
Solar Contribution: 3,130-litres @ 50 Deg C rise - annually averaged
Model: SG2-250-650e x 2
Model: G2SS1000 x 4
Model: G2EVT x 480
View fullsize
Arcare ACF Maroochydore Queensland
120-bed aged care facility
Client: Pipewise Plumbing
Solar pre-heated; 1000mJ gas fired, reticulated commercial hot/warm water system.
Peak Hour Demand: 4,410-litre @ 65 Deg C
Recovery Rate: 3,780-litres per hour @ 50 Deg C rise
Solar System: 4000 litre storage 360 evacuated tubes
Solar Contribution: 2,480-litres per day @ 50 Deg C rise – annually averaged
Model No: SG2-250-315e x 2
Model No: G2SS1000 x 4
Model No: G2EVT x 360